Request Archetype Services Field Service

Archetype Services field service is scheduled on a first come, first served basis. Three to four weeks notice is advised for booking services. For requests made within two weeks of service date, additional charges may apply.

Wattstopper

Project Information:

Requestor Information:

Jobsite Information:

All equipment shown on the Bill of Materials in your submittal has been received and installed.
All the equipment is wired and powered.
Arrangements must be made for representatives of the end user to be on site for orientation and training ofthe system (if required) There are no allowances made for return training visits unless specified in the Billof Materials.
Please note any special security measures (surrender of IDs, security clearances, escorts, training classes,etc...) required to access the site and/or Lighting Control Equipment.
Any special training/safety classes required to access site or Wattstopper equipment? (if yes, describebelow in ‘Important Notes’)
All RJ-45 cables not supplied by Wattstopper have been properly tested.
All as-built documentation is completed, accurate and submitted at least one week prior to the startup date.

FAILURE TO PROVIDE THIS INFORMATION MAY RESULT IN FORFEITURE OF YOUR SCHEDULED DATE. The as-built documentation must include:

   -Relay Panel Schedules
   -Switch Schedules
   -Networking Devices IP Information/MAC Addresses (Complete Control and DLM     Networking)
   -Other programming Information that may be required for a fully functioning     system

Lighting Control Panels:

All equipment shown is wired to the proper loads.
All low voltage switches have been installed, wires run and terminated at the proper inputs.
If using a photocell, the photosensor must be installed, wires run and terminated at the proper input(Interior and Exterior).

Complete Control Panels:

(if no LIC panel skip this section)
If using Dataline Switches, the local dataline has been run and terminated to switches...
The CC Dataline has been run and terminated to panels.(FAILURE TO USE SPECIFIED WIRE FOR DATALINES MAY JEOPARDIZE COMPLETION OF STARTUP)
A Dataline power supply has been installed and connected to the CC Dataline. This can be an externaldevice. (HDPS1CC) or a dataline power supply card installed in one of the panels (one panel will have acatalog number that ends with a ‘P’)
The front-end equipment (HLINK, HLANCC, PC, or WebLink) has been installed and connected to the CCDataline.
External communications have been wired and are available (Phone lines for phone overrides, LAN/WANwiring, etc..

DLM Lighting Control Panels:

(if no LMCP panel skip this section)
All RJ-45 cables not supplied by Wattstopper have been properly tested.(FAILURE TO USE SPECIFIED WIRE FOR DATALINES MAY JEOPARDIZE COMPLETION OF STARTUP)
All equipment relays wired to the proper loads.
All low voltage switches have been installed, wires run and terminated at the proper inputs.
If using a photocell, the photosensor must be installed, wires run and terminated at the proper input(Interior and Exterior)

DLM Lighting Control Panels:

(if no LIC panel skip this section)
All RJ-45 cables not supplied by Wattstopper have been properly tested.(FAILURE TO USE SPECIFIED WIRE FOR DATALINES MAY JEOPARDIZE COMPLETION OF STARTUP)
All equipment relays wired to the proper loads.
All low voltage switches have been installed, wires run and terminated at the proper inputs.
If using a photocell, the photosensor must be installed, wires run and terminated at the proper input(Interior and Exterior)

DLM Daylighting Systems:

(if no DLM Daylighting skip this section)
Daylighting Readiness:
  -The flooring (carpets, finished floors, etc..) have been installed.
  -The wall treatments have been completed.
  -All furniture (desks, chairs, tables, cabinets, etc..) have been unpacked,      cleaned, and installed.
  -Any window blinds or shades have been installed and fully operable.
  -Any skylight diffusers or louvers have been installed and are fully      operable.
  -All lighting fixtures have lamps installed have been tested and are     operating correctly.

DLM Dimming Systems

(if no DLM Dimming skip this section)
Lamps have been burned in per the lamp manufacturers recommendations.

DLM Networked Systems

(if no DLM Networking skip this section)
The MS/TP network (LM-MSTP) has been run and terminated between all devices/panels. (See drawingsfor details.)
The MSTP network has been installed and conforms to standard detailed in Wattstopper TechnicalBulletin #TB179.2
All IP Connectivity information is included in the ‘Request for Information – Networked Systems’ form.

Exterior Wireless

(if no Exterior Wireless skip this section)
All Connectivity Information is included in the ‘Request for Information – Exterior Wireless Systems’ form.
Lamps have been burned in per the lamp manufacturers recommendations.

Architectural Dimming Systems

(if no Architectural Dimming Systems skip this section)
Architectural Dimming Wattstopper station bus wire is installed and connected to stations.
Power over Ethernet (PoE) devices are installed and connected to Touchscreens.
If mobile apps or remote access is desired, the controller is connected to the LAN and IP connectivity isgranted (See ‘Request for Information – Architectural Dimming’ form)
Devices using RS232 or RS485 are interfaced with the controller

Architectural Dimming Systems

(if no Daylighting skip this section)
Daylighting Readiness:
  -The flooring (carpets, finished floors, etc..) have been installed.
  -The wall treatments have been completed.
  -All furniture (desks, chairs, tables, cabinets, etc..) have been unpacked,      cleaned, and installed.
  -Any window blinds or shades have been installed and fully operable.
  -Any skylight diffusers or louvers have been installed and are fully      operable.
  -All lighting fixtures have lamps installed have been tested and are     operating correctly.

Dimming Systems

(if no Architectural Dimming skip this section)
All Dimming Room Controllers have been wired and powered.
Lamps have been burned in per the lamp manufacturers recommendations.

Networked Systems

(if no Architectural Dimming Networking skip this section)
The MS/TP network (LM-MSTP) has been run and terminated between all devices/panels. (See drawings for details.)
The MSTP network has been installed and conforms to standard detailed in Wattstopper TechnicalBulletin #TB179.2
All IP Connectivity information is included in the ‘Request for Information – Networked Systems’ form.
Additional Charges:  
IF EXTRA TRIPS OR EXTRA TIME IS REQUIRED TO COMPLETE THE SYSTEM STARTUP DUE TO LACK OF PREPARATION OR INSTALLATION PROBLEMS, ADDITIONAL CHARGES TO THE CONTRACTOR MAY RESULT. THIS EXTRA WORK WILL REQUIRE A PURCHASE ORDER.  

Cancellation:  
In the event you cancel your confirmed date without reasonable notice, you may be charged to reschedule.

1. Less than 3 business days - $500.00
2. 4-7 business days - $250.00  Request  

By selecting Agree below and and pressing "Submit" the startup visit for the above-named project is hereby requested. The preparations listed above are, or will be, completed prior to the date of the startup visit. It is understood that additional trips or excess time required to complete the startup visit due to lack of preparation on the part of the installer may result in additional charges to the installer.

FAILURE TO PROVIDE THIS INFORMATION MAY RESULT IN FORFEITURE OF YOUR SCHEDULED DATE. The as-built documentation must include:

(if no LIC panel skip this section)
(if no LIC panel skip this section)